D7212GV2 | Program Entry Guide | 5.0 RADXSKED EN | 100
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
W# Open Window Start
Default: 00: 00
Selection: HH:MM (hours and minutes)
Enter the time you want the control panel to start the
Opening Window. The window goes into effect at the
beginning of the minute.
Make time entries using a 24-hour clock.
For example:
Midnight is entered as 00:00
7:00 AM is entered as 07:00
2:45 PM is entered as 14:45
11:59 PM is entered as 23:59
This program item is one of three required to create an
Opening Window. To program an Opening Window,
Open Early Begin and Open Window Stop must also
be programmed. Refer to the
W# Open Early Begin
prompt on page 99 for explanations of report features.
W# Open Window Stop
Default: 00: 00
Selection: HH:MM (hours and minutes)
Enter the time you want the control panel to end the
Opening Window. The window stops at the end of the
minute.
Make time entries using a 24-hour clock.
For example:
Midnight is entered as 00:00
7:00 AM is entered as 07:00
2:45 PM is entered as 14:45
11:59 PM is entered as 23:59
This program item is one of three required to create an
Opening Window. To program an Opening Window,
Open Early Begin and Open Window Start must also
be programmed.
If the area is not disarmed by the time the Open
Window Stop time expires, the control panel generates
a Fail to Open Report if
A# Fail to Open
is enabled
in Area-Wide Parameters.
Opening Reports generated between the Open
Window Start time and Open Window Stop time can
be suppressed by programming
A#
Disable O/C in
Window
as Yes. Refer to the
W#
Open Early Begin
prompt on page 99 for additional explanations of
report features.
Do not use a time of 23:59 as a window
stop time unless another window begins on
the next day at 00:00.
Fail to Open Reports are not sent for
windows that stop at 23:59.
Figure 5: Example Opening Window Timeline (using two Opening Windows on same day)
1
2
3
4
5
6
7
8
9
1 - Areas disarmed between midnight and 6 AM
generate Opening Reports.
2 - Areas disarmed between 6 AM and 7 AM
generate Early to Open Reports.
3 - If the area is disarmed between 7 AM and 8 AM
regular Opening Reports are generated. If Disable
O/C in Window is programmed Yes the Opening
Report is not sent to the central station.
4 - If the area is not disarmed by 8:01 AM, a Fail to
Open Event is generated if Fail to Open is
programmed Yes in Opening and Closing Options.
5 - If the user disarms the area between 8:01 AM and
12:59, PM a Late to Open Event is generated.
6 - Areas that are disarmed between 1 PM and 2
PM generate Early to Open Reports.
7 - If the area is disarmed between 2 PM and 3 PM
regular Opening Reports are generated. If
Disable O/C in Window is programmed Yes, the
Opening Report is not transmitted to the central
station.
8 - If the area is not disarmed by 3:01 PM, a Fail to
Open Event is generated if Fail to Open is
programmed Yes in Opening and Closing
Options.
9 - If the user disarms the area between 3:01 PM
and 11:59 PM, a Late to Open Event is
generated.