D7212GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 16
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
Restoral Reports are not sent if the
control panel resets after a point is
bypassed and then unbypassed. This is
true for both Fire and Non-fire points.
User Reports
Selecting Yes enables a report to be sent when the
event occurs.
Table 9: User Reports
Report Selections Report Description
R# Point
Bypass
Yes, No
Point Bypass Event
R# Forced
Point
Yes, No
Forced Point Event
R# Point
Open
Yes, No
Point Opening Event
R# Point
Close
Yes, No
Point Closing Event
R# Forced
Arm
Yes, No
Point Force Armed
R# Fail To
Open
Yes, No
Fail to Open Event
R# Fail To
Close
Yes, No
Fail to Close Event
R# Ext Clos
Tm
Yes, No
Extend Close Time
Event
R# Opening
Rpt
Yes, No
Opening Events
R# Forced
Close
Yes, No
Point Forced Close
Event
R# Closing
Rpt
Yes, No
Closing Events
R# FC Perim
Inst
Yes, No
Forced Close
Perimeter Instant
Armed Event
R# FC Perim
Delay
Yes, No
Forced Close
Perimeter Delay
Armed Event
R# Perim Inst
Arm
Yes, No
Perimeter Instant
Armed Event
R# Perim
Delay Arm
Yes, No
Perimeter Delay
Armed Event
R# Send User
Text
Yes, No
User text
Test Reports
Automatic: To send a single Test Report (
R# Test
Report
) automatically, enable Sked Function Code #9
(Test Report) in the Skeds section of the program.
Refer to Table 10.
Manual: To send a single Test Report manually, enter
[COMMAND][4][3] at the keypad. Refer to the
Send
Report
prompt on page 58.
To expand this Test Report to include any off-normal
point condition or other off-normal system conditions,
Expand Test Rpt
(refer to page 9) must be
programmed Yes. Refer to the footnotes with Table 11
on page 17 for a list of event types that are included in
an expanded test report. Additionally, the expanded
test report includes Summary Fire Supervisory,
Summary Fire Fault, Summary Controlled Point Fault,
and Summary Point Device Fault conditions.
The control panel can generate an Expanded Off-
Normal Test Report by using Sked Function Code 28
or a Non-Expanded Off-Normal Test Report using
Sked Function Code 29. To generate this event, one or
more points must be in an off-normal state at the time
the Sked executes. Expanded Off-Normal Test Reports
include the Off Normal Test Report Event as well as
panel-wide summary of off-normal point and system
conditions. Non-Expanded Off-Normal Test Report
Events are sent only when a point is in the off-normal
state but sends only the Off-Normal Test Report
Event.
Sending Status Reports
Automatic: To send a Status Report automatically that
includes the events shown in the footnotes in Table 10,
enable Sked Function Code #10 in the Skeds section
of the program.
Manual: To send a Status Report manually that
includes the events shown in the footnotes in Table 10,
enter [COMMAND][4][2] at the keypad. Refer to the
Send Report
prompt on page 58.
Sending off-normal conditions as a Status Report
following a Test Report is required by some
automation systems. Sending off-normal conditions as
a Non-status Report that follows a Test Report is
required for other automation systems.
An off-normal condition is any point that is missing,
trouble, supervisory, or in alarm. Also, points not
cleared at the keypad report as off-normal.