D7212GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 92
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
P## Report Bypass at Occurrence
Default: No
Selection: Yes or No
Yes
Send a Command Bypass Report
when the point is bypassed.
No
Do not send a Command Bypass
Report when the point is bypassed.
Send a Command Bypass Report as soon as a user
bypasses the point from the keypad. Enable this option
for all Bypassable 24-hour points. You can also report
a bypassed point at the time the area is armed. Refer
to
P## Defer BP Report
on page 92.
P## Defer BP Report
Default: No
Selection: Yes or No
Yes
Send a Point Bypass Report with the
Closing Report instead of a
Command Bypass Report when a
user bypasses the point.
No Do not defer Bypass Reports.
Use this option to prevent
P## Type
(0 to F) points
that are bypassed by the user (COMMAND BYPASS)
from occurring until the area is armed. When the area
is armed, the bypassed points and any point being
bypassed during the arming sequence report as POINT
BYPASS along with the Closing Report.
When P## Defer BP Report is set to Yes
and Closing Reports are suppressed by
using Closing Windows, the deferred
Bypass Reports are not sent.
Bypass Reports for 24-hour points do not
report If P## Report Bypass at
Occurrence and P## Defer Bypass
Report are both set to No.
To report the bypass at occurrence and
when the area is armed, program P##
Report Bypass at Occurrence and P##
Defer Bypass Report as Yes. A Command
Bypass Report is sent as soon as the user
manually bypasses a point, and a
supplemental Point Bypass Report is sent
with the Closing Report.
P## Cross Point
Default: No
Selection: Yes or No
Yes This point is a Cross point.
No This point is not a Cross point.
Do not use Cross points for Fire points.
The
P## Cross Point
option is designed to reduce
false alarms. To achieve this, program two or more
points within a Cross Point Group with this prompt
enabled. The Cross point feature is available only on
points where
P## Pt Response
is set to a value that
generates an instant alarm response.
The Cross Point feature does not activate when a fault
occurs on Controlled points (Point Types 1, 2 and 3) in
the disarmed, entry delay, or exit delay states. Refer to
Section 6.9 Cross Point Parameters on page 132 for
additional programming requirements to program the
Cross Point Timer.
If an abort window delay is needed for the cross zone
alarms, all cross zone points in the group must have
P## Alarm Abort
set to Yes (refer to page 93).
The Cross Point function applies only to
Instant Alarm conditions. It does not apply
to Trouble or Supervisory conditions.
P## Fire Point
Default: No
Selection: Yes or No
Yes This point is a Fire point.
No This point is not a Fire point.
Use this option to make a 24-hour point a Fire point.
This option makes this point the highest priority event
in the control panel when an alarm occurs for both
reporting and displaying on the keypad. Refer to
Section 4.2.2 Characteristics of a Fire Point on page 84.