D7212GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 39
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
A# Burg Time
Default: 6 min
Selection:
One min to 90 min (in one-min
increments)
Enter the number of minutes the bell rings for
Burglary Alarm points. The relay activated for this
time is programmed in
A# Alarm Bell
in Area
Relays.
The bell output begins as soon as the burglary alarm
occurs. It shuts off the bell when the programmed
number of minutes expires.
When the control panel’s internal clock begins a new
minute, it considers the first minute expired. Program
Burg Time
for two min or more.
Check with your AHJ to determine the
appropriate bell time for your
geographical area.
For SIA CP-01 Compliance:
A# Burg Time
must be 6 min or more.
A# Burg Pat
Default: Steady
Selection:
Steady, Pulse, CaStnd, TmCod3
Select the bell pattern this area uses to signal an alarm
on a Non-fire point.
Press the [SPACE] bar to scroll through the selections.
Press [ENTER] when the correct selection appears in
the display.
A# Single Ring
Default: No
Selection:
Yes or No
Yes One bell output per arming period.
After one alarm, alarms on any Non-
fire points in the same area cannot
restart the bell until the armed state
changes. An alarm on a different point
in same area restarts bell output.
No Restart bell output with each alarm
event.
Determines if an alarm from a non-fire point can
restart the alarm bell time with each Alarm Event, or
only start alarm output once per arming period.
This does not silence the keypad alarm bell tone, or
prevent any reports. This feature does not affect Fire
points. Fire points restart bell time with each new
alarm.
If and alarm occurs on a 24-hour point
while the area is disarmed, arming that
area with a key switch does not clear the
A# Single Ring flag.
Silencing the bell resets A# Single Ring.
A# Bell Test
Default: No
Selection:
Yes or No
Yes Start Bell Test.
No Do not start Bell Test.
Provides alarm output from the relay programmed at
A# Alarm Bell
after the Closing Report is confirmed
or the exit delay time expires.
Bell Test After Confirmation
In areas that send Opening and Closing Reports, the
Bell Test occurs after the control panel sends the
Closing Report and receives an acknowledgment from
the central station receiver. For proper operation of the
Bell Test after closing confirmation, the following rules
apply:
• The control panel must send Opening and Closing
Reports to the central station.
• Do not use restricted openings and closings or
Opening and Closing Windows.
Area Armed Confirmation
In areas that do not report opening and closing
activity, the alarm bell relay output for this area
activates for 2 sec after exit time expires.
Multiple Bell Tests occur: When more
than one area is armed at the same time
(such as using the ARM ALL AREAS?
function), the bell rings for 2 sec with a 2
sec pause between each bell activation if all
areas have the same exit delay time
programmed. Otherwise, the Bell Test
occurs as each area arms and it completes
its exit delay time.
When areas arm simultaneously and
report to the central station, the Bell Test
occurs as the central station receiver
confirms each area.