D7212GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 25
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
2.5 Power Supervision
AC Fail Time
Default: 1
Selection:
1 to 90 (Blank and 0 are invalid)
Program the amount of time that AC power must be
off before the control panel responds to the AC failure.
The response to restoral of AC power is delayed for
the same amount of time. The control panel always
monitors AC. The response to this prompt is the
actuation of the relay programmed in the Panel-Wide
Relays prompt
AC Failure
(refer to Section 2.13.2
Panel-Wide Relays on page 74) and the AC Fail report
enabled by the AC Fail/Res Rpt prompt. Local
annunciation of an AC failure is controlled by the
AC
Fail Display
prompt.
When you program
AC Fail Time
, if the second digit
is:
1, 3, 5, 7, or 9 (such as 3, 5, 11, 13, 15, 21, and so
on): The
AC Fail Time
interval is in minutes.
2, 4, 6, 8, or 0 (such as 2, 4, 6, 10, 12, 20, 22, and
so on): The AC Fail Time interval is in seconds.
For the following items to be true, AC
Fail/Res Rpt must be programmed as Yes
and AC Tag Along must be programmed
as No.
When you program
AC Fail Time
, if the second digit
is:
1, 3, or 5 (such as 3, 5, 11, 13, 15, 21, and so on):
The AC Fail Time interval is in minutes and an
AC Fail Event is sent after the loss of AC for this
amount of time.
No additional AC Fail Events are sent after 6
hours or 12 hours.
2, 4, or 6 (such as 2, 4, 6, 12, 14, 16, 22, 24, 26,
and so on): The AC Fail Time interval is in
seconds and an AC Fail Event is sent after the loss
of AC for this amount of time.
No additional AC Fail Events are sent after 6
hours or 12 hours.
7 (such as 7, 17, 27, 37, and so on): The AC Fail
Time interval is in minutes and an AC Fail Event
is sent after the loss of AC for this amount of time.
An additional AC Fail Event is sent after 6 hours if
the AC Fail condition is still present.
8 (such as 8, 18, 28, 38, and so on): The AC Fail
Time interval is in seconds and an AC Fail Event
is sent after the loss of AC for this amount of time.
An additional AC Fail Event is sent after 6 hours if
the AC Fail condition is still present.
9 (such as 9, 19, 29, 39, and so on): The AC Fail
Time interval is in minutes and an AC Fail Event
is sent after the loss of AC for this amount of time.
An additional AC Fail Event is sent after 12 hours
if the AC Fail condition is still present.
0 (such as 10, 20, 30, and so on): The AC Fail
Time interval is in seconds and an AC Fail Event
is sent after the loss of AC for this amount of time.
An additional AC Fail Event is sent after 12 hours
if the AC Fail condition is still present.
For the following items to be true,
AC Fail/Res Rpt
must be programmed as No and
AC Tag Along
must
also be programmed as No.
When you program
AC Fail Time
, if the second digit
is:
1, 3, or 5 (such as 3, 5, 11, 13, 15, 21, and so on):
The AC Fail Time interval is in minutes. No AC
Fail or AC Restoral Events are sent.
2, 4, or 6 (such as 2, 4, 6, 12, 14, 16, 22, 24, 26,
and so on): The AC Fail Time interval is in
seconds. No AC Fail or AC Restoral Events are
sent.
7 (such as 7, 17, 27, 37, and so on): The AC Fail
Time interval is in minutes. An AC Fail Event is
only sent after 6 hours if the AC Fail condition is
still present.
8 (such as 8, 18, 28, 38, and so on): The AC Fail
Time interval is in seconds. An AC Fail Event is
only sent after 6 hours if the AC Fail condition is
still present.
9 (such as 9, 19, 29, 39, and so on): The AC Fail
Time interval is in minutes. An AC Fail Event is
only sent after 12 hours if the AC Fail condition is
still present.
0 (such as 10, 20, 30, and so on): The AC Fail
Time interval is in seconds. An AC Fail Event is
only sent after 12 hours if the AC Fail condition is
still present.
To eliminate AC Reporting, AC Tag Along
and AC Fail/Res Rpt must be programmed
as No and the second digit of the AC Fail
Time must be a 1, 2, 3, 4, 5, or 6.