D7212GV2 | Program Entry Guide | 6.0 GV2AUX EN | 127
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
Path # Retry Count
Default: 5
Selection: 0 to 255
0
COMM FAIL RG# SDI ### Events
are not generated.
1 to 255
COMM FAIL RG# SDI ### Events
are generated after resending
Heatbeat Event the number of times
selected 5for a given SDI path.
Determines how many times the control panel resends
the Heartbeat Poll before declaring a path failure and
generating a COMM FAIL RG# SDI ### (RG # = 1
to 4, SDI ### = 88 for Path 1, 89 for Path 2, 90 for
Path 3, 91 for Path 4) Event.
The default settings meet or exceed the
UL specifications.
Path # Anti-Replay
Default: No
Selection:
Yes or No
Anti-replay is a strategy that counters “replay” attacks.
This feature prevents a malicious attack that substitutes
a control panel or another network interface module
(NIM) from delivering counterfeit events over a
network in place of events sent by the actual control
panel. A replay attack occurs when someone records a
message sent over the network by Device A, and
replays this message at a later time while pretending to
be Device A.
If this function is required, you must also
enable the Substitution Monitor function in
the Conettix D6600 Communications
Receiver/Gateway. Refer to Substitution
Monitor in the Conettix D6600/D6100
Receiver Gateway Program Entry Guide
(P/N: 4998122702) for more details.
Do not set Path # Anti-Replay to Yes if
Path # Ack Wait is set to zero (0) for the
same path.
Account Identification
The D6600 Receiver can identify the network accounts
by either the IP address or the account number
received in the message sent from the control panel.
The account number sent in the message is always the
account number for Area 1. Although you can
program up to ten digits for the account number, only
eight digits are sent in the message to the D6600
Receiver.