D7212GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 74
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
2.13.2 Panel-Wide Relays
The following eleven relay options activate when they
occur anywhere in the control panel. They are not
restricted by area boundaries.
AC Failure
Default: Blank
Selection: Blank, 1 to 24, A, B, or C
Activates when the control panel responds to an AC
power failure as programmed in
AC Fail Time
in
Section 2.5 Power Supervision on page 25. This relay
automatically resets when AC power restores.
Use this relay to create audible
annunciation. Enable the keypad’s trouble
sounders for all applications except
commercial fire systems.
Battery Trouble
Default: Blank
Selection: Blank, 1 to 24, A, B, or C
Activates when battery voltage falls below 85% of
capacity (12.1 VDC) for a fully charged (13.8 VDC)
battery, or when the battery is in a missing condition.
This relay automatically resets when battery power
restores.
Use this relay to create audible
annunciation. Enable the keypad’s trouble
sounders for all applications except
commercial fire systems.
Phone Fail
Default: Blank
Selection: Blank, 1 to 24, A, B, or C
Activates when a telephone line failure occurs. A time
must be entered in Ph Supv Time (refer to Section 2.2
Phone Parameters on page 9) for this relay to activate.
This relay resets automatically when restoral of the
phone line(s) occurs.
Comm Fail
Default: Blank
Selection: Blank, 1 to 24, A, B, or C
Activates when a control panel cannot communicate a
report after making ten attempts to each routing
destination. At the same time, COMM FAIL RT ##
displays at the keypad. This relay automatically resets
when a report is sent successfully.
Use this relay to report primary digital
report failure to an alternate communication
device.
Log % Full
Default: Blank
Selection: Blank, 1 to 24, A, B, or C
Enter the number of the relay that activates when the
log reaches the programmed percentage of its capacity,
as programmed in the
Log % Full
prompt under
GV2MAIN. This relay provides a steady output until a
Get Log and Set Pointer is executed from the remote
programming software (RPS).
Summary Fire
Default: Blank
Selection: Blank, 1 to 24, A, B, or C
Enter the number of the relay that activates when any
Fire point in the system (
P## Type 0
,
P## Fire
Yes)
enters into alarm. This relay provides a steady output
until all Fire points in the system return to normal.
Summary Alarm
Default: Blank
Selection: Blank, 1 to 24, A, B, or C
Enter the number of the relay that activates when a
Non-fire point enters into alarm. This relay provides a
steady output until the alarm is acknowledged by a
valid passcode, then cleared from alarm memory with
an acknowledgment at the keypad.
This relay does not activate for silent and
invisible alarms.