D7212GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 26
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
AC Fail Display
Default: 60 sec
Selection:
10 to 300 sec (in 5-sec increments)
Program the length of time the AC power must be off
before the message SERVC AC FAIL shows on the
keypads. The response to restoral of AC power is
delayed for the same amount of time.
AC Fail/Res Rpt
Default: No
Selection:
Yes or No
Yes Send AC Fail and AC Restoral
Reports.
No Does not send AC Fail and AC
Restoral Reports.
AC Power Supervision Reports are sent to the central
station and local printer at the time programmed for
AC Fail Time
.
AC Tag Along
Default: Yes
Selection:
Yes or No
Yes Send AC messages as tag along
events.
No Do not send AC messages as tag
along events.
Send AC Reports only if any other event occurs while
AC is off-normal.
If AC Tag Along is set to Yes and a
subsequent event is generated, the AC
Fail Event is sent first, before sending any
subsequent events.
AC Tag Along is required for NFPA and
UL 864 commercial fire systems. Be sure
to program AC Fail/Res Rpt as No if AC
Tag Along is programmed Yes.
AC/Battery Buzz
Default: No
Selection:
Yes or No
Yes Initiates panel-wide trouble tone at all
keypads.
No Does not initiate panel-wide trouble
tone at keypads
Initiates a panel-wide trouble tone at keypads when
AC fails or battery is low or missing. This program
item does not prevent the SERVC AC FAIL or SERVC
BATT LOW displays.
To comply with NFPA standards and UL
864 requirements for commercial fire
systems, program this item as Yes.
If annunciating panel-wide troubles at a
keypad with CC# Scope set to Panel Wide
is undesirable, set CC# Trouble Tone to
No. Refer to Section 2.10 Keypad
(Command Center) on page 46 for keypad
configurations.
Bat Fail/Res Rpt
Default: Yes
Selection:
Yes or No
Battery Failure and Restoral Reports are sent
to the central station. They are routed to the
telephone number programmed for
Power/Phone Events.
Modem
Reports
Missing or
shorted
Discharged
below 12.1
VDC
BATTERY
MISSING
BATTERY LOW
Yes
BFSK
Reports
Missing, shorted
low battery
TROUBLE
ZONE 9
No
Battery Failure and Restoral Reports are not
sent to the central station.